DL05/06 Speciality modules
Expand the Capabilities of the DL05 DL05 (and DL06) PLCs can be customized to fit the requirements of applications by adding option modules in the built-in slots. One slot for the DL05 and four slots for the DL06. Features are added without increasing the footprint (size) of the PLC.
DL05/06 option module functions include:- Discrete I/O
- Analogue I/O
- Communications
- Specialty modules
Specialty Option Modules:- F0-CP128 Triple-port BASIC, ASCII Overdrive CoProcessor Module
- H0-CTRIO High-speed Counting/ Pulse Output Module
- D0-01MC Memory Cartridge
- F0-08SIM Input Simulator Module
|  |
|
DL05/06: Triple-port BASIC, ASCII Overdrive CoProcessor Module | 
| Triple-port BASIC, ASCII Overdrive CoProcessor Module interfaces the DL05/06 family of programmable controllers with bar code readers, operator interface terminals, instrumentation equipment, computers and other serial devices.Applications: BASIC CoProcessors are designed for use with intelligent devices such as:
- Bar code readers
- Welders
- Board level controllers
- Serial printers
- Intelligent sensors
- Almost any device with an RS232C or RS485 port
Features Include:
- Extended BASIC and ABM Commander for Windows software for PCs makes program development fast and simple.
- Non-volatile memory of up to 128 K allows multiple program storage and execution, DL05/06 register expansion, and retentive data storage and retrieval.
- 100 MHz BASIC CoProcessor provides fast program execution independent of the CPU scan.
- Three buffered ports permit communication from the module to three external devices.
- A real-time clock/calendar maintains time/date with battery backup when power outages occur. Programmable time based BASIC interrupts to 5 ms.
- Direct access of up to 256 bytes of DL05/06 CPU memory per scan is possible. No supporting ladder logic is required.
- Floating point math solves complex formulas to eight significant digits.
- An RJ12 Port 1 and Port 3 splitter is included with the module. This will provide easy connection of RS-232 cables to both Port 1 and Port 3. (If you are using RTS1 and CTS1 for port 1, then port 3 is not available.)
|
|
DL05/06: High-speed Counting/ Pulse Output Module | 
| The High-Speed Counter I/O (H0-CTRIO) module is designed to accept high-speed pulse-type input signals for counting or timing applications and designed to provide high-speed pulse-type output signals for stepper/ servo motor control, monitoring, alarm or other discrete control functions.
The H0-CTRIO module offers great flexibility for applications that call for precise counting or timing, based on an input event or for high-speed control output applications. The H0-CTRIO module has its own microprocessor and operates asynchronously with respect to the PLC/Controller. This means the on-board outputs respond in real time to incoming signals so there is no delay waiting for the PLC/Controller to scan I/O.
The H0-CTRIO module is designed to work with incremental encoders or other field devices that send pulse outputs. You can use the H0-CTRIO module with any of the DLO5 or DL06 PLCs.
H0-CTRIO - High Speed Counter Interface Module
- 4 DC sink/ source inputs 9-30 VDC, 2 isolated sink/ source DC outputs, 5-30 VDC, 1 A per point.
- Inputs supported: 1 quadrature encoder counters up to 100 KHz, or 2 single channel counters up to 100 KHz, and 2 high speed discrete inputs for Reset, Inhibit, or Capture.
- Outputs supported: 2 independently configurable high speed discrete outputs or 1 channel pulse output control, 20 Hz-25 KHz per channel, pulse and direction or cw/ ccw pulses.
|
|

| Note: Manuals do not come with our products unless specified in the description. Download manual from our web site at no charge, or order manual separately.Note: New option modules may not be supported by CPUs purchased prior to the modules release. You can refer to the module specification page on our Web site for this information or find it in our catalog. Be sure to check for the latest firmware for your PLC. Here is the direct link to the Firmware Upgrade section of our Web site where you can find the firmware revision histories, the latest files and tools required to download the firmware into your CPU.Note: Power budget limitations restrict the number of modules allowed in the expansion slots of DL05 and DL06 bases. Please consult the power budgeting tables in your manual or catalogue for specific calculations. Calculate the power budget | |
|